LPS Emergency Power Systems
Inverters
Description
- Midsize-electrical inverter systems for powering up to 375W - 600W or up to 750W - 1150W of incandescent, fluorescent, induction or LED lighting loads. Pulse with modulated (PWM) output design provides clean, 60Hz sinusoidal emergency power to loads
- All models are designed for fast, easy wall mounting
Electrical Specifications
INPUT
- Input Voltages: Universal 120 or 277VAC, 60Hz (User selectable with (2) wire jumpers provided)
- Input Frequencies: 60Hz ± 2%
- Input Surge Protection: Meets UL924
- Input Protection: Provided by Service Panel rated at 20 Amps MAX
OUTPUT
- Output Voltages: 60Hz 120-277VAC
- Efficiency Rating: 98% at full rated load (line)
- Waveform: Sinusoidal (digitally controlled)
- Static Voltage: ±5% during battery discharge; 0-100% liner load
- Output Frequencies: 60Hz ±0.3Hz during emergency cycle
- Output Distortion: Less than 3% THD (linear load)
- Transfer Time: Less than 1.0 second
- Load Power Factor Range: 0.88 Lead to 0.88 Lag
- Minimum Loading: 0% of rated system capacity
- Output Protection: Circuit breaker
- Output Protection: Overload shut down protection (750W-1150W model only)
Housing
- Heavy duty steel cabinet is finished in white baked-on powder paint providing scratch and corrosion resistance
- Optional special color paint (-SP) finishes are available
Mounting
- Surface Mount: Surface mount models are designed for mounting to walls by means of keyhole slots provided in the back of the unit housing
Warranty / Listing
- Unit (excluding lamps): Full coverage against defects in materials and workmanship for 3 years from date of shipment
- Battery: 3 years full warranty plus an additional 7 years of pro-rata coverage
- All models are UL924 Listed and meet NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes
- UL Listed for Damp Locations (20° - 30°C)
- Certified to CEC under Title 20 Regulations
- FCC Part 15 Class A Compliant (750W-1150W model only)
The LPS Series is designed to provide Emergency Power to incandescent, fluorescent, induction and/or LED fixtures. The LPS provides power to the input side of the fixture (including the ballast), eliminating any chance on incompatibility. For more details - please check LPS Emergency Power Systems Spec Sheets at Downloads tab.